Summary

Flow pattern observations and measurements of the heat transfer in a helical grooved micro fin tube are presented and compared with results for a smooth tube. The micro fin tube used (OD of 9.52 mm) is a Wieland Cuprofin EDX tube with 60 fins (height 0.25 mm) and a helix angle of 18°. The flow pattern observations at 39.7 and 26.4 bars show a wide range of the annular flow region. The transition from slug to annular flow does not occur, as expected, at constant vapour quality for all mass fluxes but there is an interdependence between transition vapour quality and mass flux. For the heat transfer in the micro fin tube, measurements at 39.7 bars are presented for heat fluxes up to 120 kW/m2, mass fluxes between 75 and 250 kg/m2.s and vapour qualities between 0.1 and 0.9.

Available documents

Format PDF

Pages: 1186-1195

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Flow pattern and heat transfer characteristics during flow boiling of CO2 in a horizontal micro fin tube and comparison with smooth tube data.
  • Record ID : 2006-0625
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 28 - n. 8
  • Publication date: 2005/12