IIR document

Heat transfer and pressure drop during hydrocarbon refrigerant condensation inside a brazed plate heat exchanger.

Author(s) : LONGO G. A.

Type of article: Article, IJR article

Summary

This paper presents the heat transfer coefficients and pressure drop measured during HC-600a, HC-290 and HC-1270 saturated vapour condensation inside a brazed plate heat exchanger: the effects of refrigerant mass flux, saturation temperature (pressure) and fluid properties are investigated. The heat transfer coefficients show weak sensitivity to saturation temperature (pressure) and great sensitivity to refrigerant mass flux and fluid properties. A transition point between gravity controlled and forced convection condensation has been found for a refrigerant mass flux around 15-18 kg/m2.s. In the forced convection condensation region the heat transfer coefficients show a 35-40% enhancement for a 60% increase of the refrigerant mass flux. The frictional pressure drop shows a linear dependence on the kinetic energy per unit volume of the refrigerant flow. HC-1270 shows heat transfer coefficients 5% higher than HC-600a and 10-15% higher than HC-290, together with frictional pressure drop 20-25% lower than HC-290 and 50-66% lower than HC-600a.

Available documents

Format PDF

Pages: pp. 944-953

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Heat transfer and pressure drop during hydrocarbon refrigerant condensation inside a brazed plate heat exchanger.
  • Record ID : 2010-0742
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 33 - n. 5
  • Publication date: 2010/08

Links


See other articles in this issue (14)
See the source