Hybrid HVAC systems with chemical dehumidification for supermarket applications.
Author(s) : CAPOZZOLI A., MAZZEI P., MINICHIELLO F., et al.
Type of article: Article
Summary
HVAC systems in supermarkets must assure both thermal comfort for occupants and suitable climatic conditions for refrigerated cases, which operate better with low ambient relative humidity (40-45%). Since open display cases substantially reduce sensible load and moderately reduce latent load, ambient sensible/total heat load ratio is less than usual. Thus, if dehumidification is carried out with a traditional cooling coil, over-sizing of the coil and re-heating of the treated air are necessary, with energy and economic waste. To offset these disadvantages, hybrid HVAC systems with chemical dehumidification may be employed. In this paper a case study is presented in which a traditional HVAC system is compared to hybrid systems with chemical dehumidification. Dynamic simulation codes (DOE and DesiCalcT) and test reference year data, opportunely elaborated, have been used. Annual operating costs have been estimated and large savings have been obtained with hybrid systems. Considerable reduction of electric energy demand as well as better control of thermal-hygrometric conditions were noted. A simple payback of about 1 year has been obtained. Finally, a virtual retrofitting operation on 30% of the existing HVAC systems in Italian supermarkets has shown significant operating cost savings. [Reprinted with permission from Elsevier. Copyright, 2005].
Details
- Original title: Hybrid HVAC systems with chemical dehumidification for supermarket applications.
- Record ID : 2006-2614
- Languages: English
- Source: Applied Thermal Engineering - vol. 26 - n. 8-9
- Publication date: 2006/06
Links
See other articles in this issue (8)
See the source
Indexing
- Themes: Comfort air conditioning
- Keywords: Ventilation; Design; Adsorption system; Supermarket; Expérimentation; Dehumidifier; Air conditioning
-
The primary research on liquid desiccant dehumi...
- Author(s) : WU A. M., LI C. L., ZHANG H. F.
- Date : 2006/07/17
- Languages : English
- Source: 2006 Purdue Conferences. 18th International Compressor Engineering Conference at Purdue & 11th International Refrigeration and Air-Conditioning Conference at Purdue [CD-ROM].
- Formats : PDF
View record
-
Design and performance evaluation of a novel mu...
- Author(s) : SHAMIM J. A., HSU W. L., DAIGUJI H.
- Date : 2017/08/07
- Languages : English
- Source: International sorption heat pump conference, ISHPC 2017, Tokyo august 7-10.
View record
-
Experimental investigation on the local air age...
- Author(s) : WANG F., LI Y., LIU X., et al.
- Date : 2009/05/20
- Languages : English
- Source: ACRA-2009. The proceedings of the 4th Asian conference on refrigeration and air conditioning: May 20-22, 2009, Taipei, R.O.C.
- Formats : PDF
View record
-
Numerical study on internally cooled-heated deh...
- Author(s) : YIN Y., ZHANG X. S.
- Date : 2007/08/21
- Languages : English
- Source: ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
- Formats : PDF
View record
-
FIELD MONITORING OF THE WINTER PERFORMANCE OF A...
- Author(s) : TSONGAS G. A., WRIDGE R. S.
- Date : 1989
- Languages : English
View record