Liquid-flooded Ericsson cycle cooler. 1. Thermodynamic analysis.

Author(s) : HUGENROTH J., BRAUN J., GROLL E., et al.

Summary

A novel implementation of a gas Ericsson cycle heat pump is presented. The concept uses liquid flooding of the compressor and expander to approach isothermal compression and expansion processes. A thermodynamic analysis of the cycle was performed using an EES-based computer model. In the ideal case with reversible components, the COP of the cooler approaches the Carnot COP as the liquid flooding is increased. However, in the nonideal case when the rotating machinery operates irreversibly, there is an optimal liquid flooding rate and pressure ratio that produces the best performance. As with all gas cycles, the performance of the liquid flooded Ericsson cycle cooler is very sensitive to the efficiency of the compressor and expander. Results for two cycle configurations are presented. See also this Bulletin, reference 2007-1747.

Available documents

Format PDF

Available

  • Public price

    20 €

  • Member price*

    15 €

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Liquid-flooded Ericsson cycle cooler. 1. Thermodynamic analysis.
  • Record ID : 2007-1746
  • Languages: English
  • Source: 2006 Purdue Conferences. 18th International Compressor Engineering Conference at Purdue & 11th International Refrigeration and Air-Conditioning Conference at Purdue [CD-ROM].
  • Publication date: 2006/07/17

Links


See other articles from the proceedings (157)
See the conference proceedings