MEASUREMENTS ON A 60 KILOWATT AIR-TO-AIR HEAT PUMP PLANT.
[In Norwegian. / En norvégien.]
Author(s) : NESJE O.
Type of article: Article
Summary
THE PRESENT PAPER CONTAINS RESULTS FROM MEASUREMENTS CARRIED OUT ON A 60 KILOW AIR-AIR HEAT PUMP. COP VARIES FROM 2.6 TO 4.25, DEPENDING ON OUTSIDE TEMPERATURE AND THE AIR SPEED THROUGH THE EVAPORATORS. THE FRONT VELOCITY DEPENDS ON THE OUTSIDE TEMPERATURE AND VARIES IN THE RANGE 1.3 TO 2.3 (M/S). THE THERMODYNAMIC LOSSES (EXERGY LOSSES) WHICH OCCUR IN DIFFERENT COMPONENTS ARE CALCULATED WITH BASIS IN RESULTS FROM MEASUREMENTS. HOW THESE LOSSES ARE INFLUENCED BY THE FRONT VELOCITY ARE PRESENTED.
Details
- Original title: [In Norwegian. / En norvégien.]
- Record ID : 1987-0300
- Languages: Norwegian
- Source: Scand. Refrig. - vol. 15 - n. 3
- Publication date: 1986/06
- Document available for consultation in the library of the IIR headquarters only.
Links
See other articles in this issue (1)
See the source
Indexing
- Themes: Heat pumps techniques
- Keywords: High capacity; Exergy; Measurement; Air-air; Heat pump; Performance; Norway; COP
-
OPERATIONAL EXPERIENCE WITH A 10 MW DIESEL DRIV...
- Author(s) : FANE O.
- Date : 1983
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 6 - n. 3
- Formats : PDF
View record
-
3 MW EFFLUENT HEAT PUMP. MEASUREMENTS AND EXPER...
- Author(s) : LINDSTROM H., TROSELIUS L.
- Date : 1985
- Languages : Swedish
- Source: Swed. Counc. Build. Res. - R34:1985; 33 p.; fig.
View record
-
DEVELOPMENT OF ADVANCED WATER-TO-WATER HEAT PUM...
- Author(s) : GILLI P. V.
- Date : 1986
- Languages : English
- Source: Swed. Counc. Build. Res. - D17:1986; 140 p.
View record
-
CO2 refrigerant in large heat pumps: transcriti...
- Author(s) : LORENTZEN G.
- Date : 1994/03
- Languages : English
- Source: IEA HPC Newsl. - vol. 12 - n. 1
View record
-
LARGE HEAT PUMP INSTALLATIONS.
- Author(s) : BARTMANN H., LANG J.
- Date : 1987/01
- Languages : German
- Source: Tech. Bau - n. 1
View record