Meniscus galvanic corrosion: a source of refrigerant leakage.

Author(s) : LIEBERMAN E.

Type of article: Article

Summary

The article describes a form of galvanic corrosion that can develop between closely spaced, but non-contacting, aluminum and copper tubing used in refrigeration applications. It results in a pin hole developing in the aluminum tubing, causing a complete loss of refrigerant.

Details

  • Original title: Meniscus galvanic corrosion: a source of refrigerant leakage.
  • Record ID : 1996-2219
  • Languages: English
  • Source: Air Cond. Heat. Refrig. News - vol. 196 - n. 16
  • Publication date: 1995/12/18
  • Document available for consultation in the library of the IIR headquarters only.

Links


See the source