MOTHER NATURE'S LEGACY: COIL FROST.
Author(s) : JOHNSON R. J. Jr
Summary
THE PAPER IS VIRTUALLY A DESIGN CHECK LIST FOR THE SUCCESSFUL DEFROSTING BY HOT GAS OF AMMONIA REFRIGERATION COILS. BASIC RULES SUCH AS, ALWAYS TO ENSURE 2/3 TO 3/4 OF EVAPORATOR SURFACE IS OPERATING NORMALLY WHILE THE REMAINDER IS DEFROSTED, AND ALWAYS ENSURE ADEQUATE FREE DRAINAGE OF CONDENSATE FROM DEFROSTING EVAPORATORS, ARE ENLARGED TO SUGGEST VARIOUS METHODS OF PIPING ANDCONTROL TO COVER MOST APPLICATIONS OF DIRECT EXPANSION, FLOODED, AND PUMP FEED EVAPORATORS. D.W.H.
Details
- Original title: MOTHER NATURE'S LEGACY: COIL FROST.
- Record ID : 1989-0948
- Languages: English
- Publication date: 1988/03/06
- Source: Source: IIAR, 10th annu. Meet., Savannah, GA
251-259; 3 fig. - Document available for consultation in the library of the IIR headquarters only.
Indexing
-
Hot gas defrost systems for large flooded evapo...
- Author(s) : BRILEY G. C., LYONS T. A.
- Date : 1992/04/22
- Languages : English
View record
-
ENERGY CONSIDERATIONS IN HOT-GAS DEFROSTING OF ...
- Author(s) : STOECKER W. F., LUX J. J. Jr, KOOY R. J.
- Date : 1983
- Languages : English
View record
-
SELECTION AND APPLICATION OF A REFRIGERATING UN...
- Author(s) : MURAI S.
- Date : 1984
- Languages : Japanese
- Source: Refrigeration - vol. 59 - n. 683
View record
-
Selecting the size of pipes carrying hot gas to...
- Author(s) : STOECKER W. F.
- Date : 1984/07
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 7 - n. 4
- Formats : PDF
View record
-
Hot gas defrost of low temperature refrigeratio...
- Author(s) : MIKHAILOV A., KORTSTEE J.
- Date : 2012/06/25
- Languages : English
- Source: 10th IIR-Gustav Lorentzen Conference on Natural Working Fluids (GL2012). Proceedings. Delft, The Netherlands, June 25-27, 2012.
- Formats : PDF