Performance of a transcritical CO2 heat pump for simultaneous water cooling and heating.
Author(s) : SARKAR J., BHATTACHARYYA S., RAM GOPAL M.
Summary
This paper presents the experimental as well as the simulated performance studies on the transcritical CO2 heat pumps for simultaneous water cooling and heating; effects of water mass flow rates and water inlet temperatures of both evaporator and gas cooler on the cooling and heating capacities, system COP and water outlets temperatures are investigated. Study shows that both the water mass flow rate and inlet temperature have significant effect on system performances. Test results show that the effect of evaporator water mass flow rate on the system performances and water outlet temperatures is more pronounced (COP increases 0.6 for 1 kg/min) compared to the gas cooler water mass flow rate (COP increases 0.4 for 1 kg/min) and the effect of gas cooler water inlet temperature is more significant (COP decreases 0.48 for given ranges) compared to the evaporator water inlet temperature (COP increases 0.43 for given ranges). Comparisons of experimental values with simulated results show the maximum deviation of 5% for cooling capacity, 10% for heating capacity, 16% for system COP. This study offers useful guidelines for selecting appropriate water mass flow rate to obtain required system performance.
Details
- Original title: Performance of a transcritical CO2 heat pump for simultaneous water cooling and heating.
- Record ID : 2010-0262
- Languages: English
- Source: 2009 ASHRAE Annual Conference CD. Transactions papers presented at the 2009 ASHRAE Annual Conference: Louisville, KY, June 2009. Volume 115, part 2.
- Publication date: 2009/06/21
Links
- External links:
See other articles from the proceedings (30)
See the conference proceedings
Indexing
-
Themes:
Heat pumps techniques;
CO2 - Keywords: Comparison; Simulation; Heat pump; Performance; Expérimentation; Transcritical cycle; COP; Refrigerant; Water-water; CO2
-
An experimental study on the performance of a h...
- Author(s) : KUO C. S., NIAN S. H., CHAO L. Y.
- Date : 2009/09/02
- Languages : English
- Source: Compressors 2009: 7th International Conference on Compressors and Coolants
- Formats : PDF
View record
-
Static simulation and experiment of CO2 heat pu...
- Author(s) : KATO D., YAMAGUCHI S., SAITO K., et al.
- Date : 2008/09/07
- Languages : English
- Source: 8th IIR-Gustav Lorentzen Conference on Natural Working Fluids (GL2008)
- Formats : PDF
View record
-
Optimización de un ciclo transcrítico de N2O: s...
- Author(s) : SARKAR J., BHATTACHARYYA S.
- Date : 2010/09
- Languages : Spanish
- Source: IIF-IIR/Frío Calor Aire acond. - vol. 38 - n. 428
- Formats : PDF
View record
-
Optimization of a transcritical N2O refrigerati...
- Author(s) : SARKAR J., BHATTACHARYYA S.
- Date : 2008/09/07
- Languages : English
- Source: 8th IIR-Gustav Lorentzen Conference on Natural Working Fluids (GL2008)
- Formats : PDF
View record
-
Performance optimization of a transcritical CO2...
- Author(s) : RULLIERE R., COLASSON S., HABERSCHILL P.
- Date : 2009/06/23
- Languages : English
- Source: 3rd Conference on Thermophysical Properties and Transfer Processes of Refrigerants
- Formats : PDF
View record