IIR document

Performance of integrated R744-packs part 1: compressor mass flow estimation based on data-driven models using analytical methods and actual field measurements

Summary

Rising concerns for climate change impacts along with the new legislation aimed at lowering emissions indicates the inevitable transition in the cooling/heating industry towards a more energy-efficient solution with minimal environmental impact. Integrated refrigeration, air condition and heat recovery solutions by CO2 (R744) packs are efficient solutions to high energy demanding building (supermarkets and hotels). Proven performance enhancement of Multi Ejector SolutionTM makes the R744 systems more energy efficient, especially in warm climates, compared to the most conventional synthetic refrigerant systems in food retail applications.
Pilot installation in the frame of MultiPACK, an EU funded project (Horizon 2020), provided a wide range of data, offering the possibility of evaluating the real performance of each ejector group: high pressure (HP), low pressure (LP) and liquid ejector (LE), by running the system in different operating modes. Analysis of the data indicated performance improvement of a system with ejector, on average a 35% lower energy consumption compared to baseline parallel compression R744 system without ejectors.
Availability of mass flow measurement, 5 Coriolis mass flow meters on this pilot, enabled the possibility of comparison of mass flow rate estimation based on data acquisition from compressors with actual
measurement. Methods utilized include: Energy balance, volumetric displacement, manufacturer polynomials, and data-driven method. The comparison reveals the importance of compressor suction and
discharge parameters for obtaining reliable results based on energy balance, volumetric displacement, manufacturer polynomials methods. The current study shows data-driven method performs well after
enough training time with error bounded to 3% and 10 % on low and medium temperature level compressors, respectively.

Available documents

Format PDF

Pages: 9

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Performance of integrated R744-packs part 1: compressor mass flow estimation based on data-driven models using analytical methods and actual field measurements
  • Record ID : 30028217
  • Languages: English
  • Subject: HFCs alternatives
  • Source: 10th IIR Conference on Compressors and Refrigerants.
  • Publication date: 2021/01/13
  • DOI: http://dx.doi.org/10.18462/iir.compr.2021.0390
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles from the proceedings (35)