Refrigerant R-410A vaporisation inside a small brazed plate heat exchanger.

Author(s) : LONGO G. A., GASPARELLA A.

Summary

This paper presents the experimental heat transfer coefficients and pressure drop measured during refrigerant R-410A vaporisation inside a small brazed plate heat exchanger: the effects of heat flux, refrigerant mass flux, saturation temperature and outlet conditions are investigated. The experimental results are reported in terms of refrigerant side heat transfer coefficients and frictional pressure drop. The heat transfer coefficients show high sensitivity both to heat flux and outlet conditions and weak sensitivity to saturation temperature. The frictional pressure drop shows high sensitivity to refrigerant mass flux and weak sensitivity both to saturation temperature and outlet conditions. The experimental heat transfer coefficients are also compared with two well-known correlations for nucleate pool boiling: a fair agreement is found.

Available documents

Format PDF

Available

  • Public price

    20 €

  • Member price*

    15 €

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Refrigerant R-410A vaporisation inside a small brazed plate heat exchanger.
  • Record ID : 2008-2028
  • Languages: English
  • Source: 2006 Purdue Conferences. 18th International Compressor Engineering Conference at Purdue & 11th International Refrigeration and Air-Conditioning Conference at Purdue [CD-ROM].
  • Publication date: 2006/07/17

Links


See other articles from the proceedings (157)