IIR document

Risk inherent in the use of counterfeit refrigerants, 23rd Informatory Note on refrigerating technologies.

Author(s) : IIF-IIR, CAVALIER G., LAWTON R.

Type of article: Informatory note

Summary

Several cases of explosions occurring in marine refrigerated containers (reefers) have been reported in various parts of the world in recent months. Besides causing major material damage, these accidents have resulted in the deaths of several operators. The assessments performed following these accidents have established that these explosions were due to the use of counterfeit refrigerants containing R40 (methyl chloride, also known as chloromethane, CH3Cl) mixed with R134a, the refrigerant initially used in these units. The goals of this Note are to raise the awareness of operators concerning this new risk, to propose a detection method designed to detect systems containing counterfeit refrigerants that thus constitute a risk, and to examine ways of decontaminating contaminated systems. The aim is also to attract the attention of public authorities and decision-makers regarding the impact of counterfeit refrigerants on the refrigeration sector, with respect to safety and also in economic terms.

Available documents

Informatory Note - Risk inherent in the use of counterfeit refrigerants (English)

Pages: 3 p.

Available

Free

23e Note d'Information - Risques des frigorigènes contrefaits - Version française

Pages: 3 p.

Available

Free

Details

  • Original title: Risk inherent in the use of counterfeit refrigerants, 23rd Informatory Note on refrigerating technologies.
  • Record ID : 30006356
  • Languages: English, French
  • Source: IIF, Note Inf. Technol. Froid / IIR, Inf. Note Refrig. Technol. / www.iifiir.org - n. 23
  • Publishers: IIF-IIR
  • Publication date: 2012/11
  • Document available for consultation in the library of the IIR headquarters only.

Links


See the source