IIR document

Shell side plain tube bundle performance of a multi-pass direct expansion evaporation of ammonia at various degrees of exit superheat.

Author(s) : ABBAS A., AYUB Z. H., AYUB A. H., et al.

Type of article: Article, IJR article

Summary

This paper presents the experimental results of shell side dry expansion evaporation characteristics of ammonia on a triangular pitch plain tube bundle in a multi pass cross flow configuration evaporator. Heat exchanger had 4 passes with 3 plain tubes in each pass. The average bundle heat transfer coefficient showed better performance at -1.7 °C versus -20 °C. Heat transfer performance of individual passeswere studied at saturation temperature of -1.7 and -20 °C, heat flux range of 5 to 45 kW m-2 and exit superheat temperature of 2 to 10 °C. Present data suggest that variation in bundle performance is less significant at lower heat fluxes with low degree of exit superheat. Top pass with maximum quality along the bundle height showed the least performance with increase in the degree of exit superheat.

Available documents

Format PDF

Pages: 70-82

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Shell side plain tube bundle performance of a multi-pass direct expansion evaporation of ammonia at various degrees of exit superheat.
  • Record ID : 30021561
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 78
  • Publication date: 2017/06
  • DOI: http://dx.doi.org/10.1016/j.ijrefrig.2017.03.020

Links


See other articles in this issue (15)
See the source