System performance test results of R407A (HFC32-HFC125-HFC134a: 20-40-40%) compared to R502.

Summary

Measurements were conducted at two different condensing temperatures, 54,4 and 43,3 deg C. The refrigerant evaporating temperature was varied over a range of -30 to -15 deg C. The relative evaporator capacity of R407A compared to R502 was found to range from 0,93 to 1,07 depending on the operating conditions and the amount of liquid subcooling present. For all conditions tested R407A had higher energy efficiency than R502. The relative COP of R407A ranged from 1,01 to 1,06.

Available documents

Format PDF

Pages: 191-198

This document is to be digitised and will be available within 10 working days

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: System performance test results of R407A (HFC32-HFC125-HFC134a: 20-40-40%) compared to R502.
  • Record ID : 1995-1516
  • Languages: English
  • Source: CFCs, the Day After.
  • Publication date: 1994/09/21