The method of calculating the temperature of an evaporation-cooled surface by using wet-bulb temperature.

[In Japanese. / En japonais.]

Author(s) : KONNO Y., SHIMADA K., ENAI M.

Type of article: Article

Summary

In order to obtain the temperature of the evaporation-cooled outer surface of a building, which is exposed to solar radiation, by wetting the surface with water as in the case of spraying water onto the roof, it was necessary to set up a thermal equilibrium equation for the wet surface and conduct convergent calculation because the saturated water vapour pressure is nonlinear with regard to temperature. In this report, a method is proposed which enables easy calculation of the temperature of an evaporation-cooled surface by taking into account the similarity between the evaporation-cooled surface temperature and the wet bulb temperature closely related to the wet surface.

Details

  • Original title: [In Japanese. / En japonais.]
  • Record ID : 2007-2736
  • Languages: Japanese
  • Source: Transaction of the Society of Heating, Air-conditioning and Sanitary Engineers of Japan - n. 125
  • Publication date: 2007/08

Links