The transient response of capacitive thin-film polymer humidity sensors.
Author(s) : DOOLEY J. B., O'NEAL D. L.
Type of article: Article
Summary
The transient response of capacitive thin-film polymer humidity sensors to step changes in humidity and temperature as a function of air velocity was investigated. Two duct-mounted humidity sensors (designated Candidate X and Candidate Y) from two manufacturers, each with thin-film capacitive humidity sensing elements and temperature output, were used in the study. The transient performance of each test sensor was characterized by measuring the time constants of the relative humidity (RH) and temperature outputs in response to step changes in RH and temperature over a range of air velocities. Duct air velocities of 0 (still air), 200, 500, 800, and 1100 ft/min (0, 1.0, 2.5, 4.1, and 5.6 m/s) were considered along with step changes in RH of 20-40% and step changes in air temperature of 0°F (isothermal), 9°F, and 18°F (0, 5, and 10°C). The effects of a positive or negative RH step change direction (lower to higher RH and vice versa) were also considered. Results showed that the RH time constants of both sensors decreased asymptotically with increasing duct air velocity for all testing conditions. For the isothermal tests, the average RH time constants of the Candidate X and Y sensors were approximately 4 and 18 s, respectively. When a step change in temperature was introduced, the RH time constants increased by factors of 100 and 12 over the isothermal values, respectively. With the exception of the still-air tests, the time constant of the Candidate X sensor for negative RH step changes was, on average, about 65% less than compared to positive RH step changes. For the Candidate Y sensor, a time-constant dependency on RH step-change direction was not observed.
Details
- Original title: The transient response of capacitive thin-film polymer humidity sensors.
- Record ID : 2008-2439
- Languages: English
- Source: HVAC&R Research - vol. 14 - n. 5
- Publication date: 2008/09
Links
See other articles in this issue (7)
See the source
Indexing
-
Prediction of skin and clothing temperatures un...
- Author(s) : UMENO T., HOKOI S., TAKADA S.
- Date : 2001
- Languages : English
- Source: ASHRAE Transactions. 2001 Winter Meeting, Atlanta, GA. Volume 107, part 1 + CD-ROM.
View record
-
Les capteurs nouvelle génération.
- Date : 2006/12
- Languages : French
- Source: Process - n. 1232
View record
-
Transient humidity measurements for flow throug...
- Author(s) : WANG Y. H., BESANT R. W., SIMONSON C. J., et al.
- Date : 2005
- Languages : English
- Source: ASHRAE Transactions. 2005 Annual Meeting, Denver, Colorado, USA. Volume 111, part 2 + CD-ROM.
View record
-
The search for high temperature experimental ps...
- Author(s) : SAUER H. J. Jr, NELSON H. F., HUANG X.
- Date : 2001/06/24
- Languages : English
- Source: ASHRAE Transactions. 2001 annual Meeting, Cincinnati, Ohio. Volume 107, part 2 + CD-ROM.
View record
-
An overview of room air motion measurement: tec...
- Author(s) : SUN Y., ZHANG Y.
- Date : 2007/11
- Languages : English
- Source: HVAC&R Research - vol. 13 - n. 6
View record