Summary
Propane (R290) is a promising refrigerant for split-type household air conditioners with the advantages of energy saving, environmentally friendliness and low charge. Nevertheless, the large scale use of R290 has been hindered by its high flammability. The potential fire hazards can be relieved by reducing R290 releasable charge, and numerous methods have been put forward. In the authors’ previous papers, the method of refrigerant pump-down was proposed and a mathematical model of critical releasable charge (CRC, ignition threshold of leakage) was developed by dimensional analysis, but it is difficult to reflect the actual physical process of R290 dispersion. To reveal the leakage and dispersion mechanism of R290, a new numerical model of CRC is developed based on mechanism analysis in this work, in which the turbulent jet model, Coanda effect and dimensional analysis are involved. The predicted CRCs agree well with experimental and simulated data. Besides, the influence of indoor air speed with its direction parallel to the IDU panel on R290 concentration field is investigated by computational fluid dynamics (CFD) under different releasable charges. It is found that there is a transition value of air speed, below which the fire hazards decrease greatly with the increase of air speed, on the contrary, when the air speed is above the transition value, raising air speed has little impact on fire hazards.
Available documents
Format PDF
Pages: 139-148
Available
Public price
20 €
Member price*
Free
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: Theoretical and simulation analysis for R290 leakage from split-type air conditioners.
- Record ID : 30032599
- Languages: English
- Subject: Technology
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 166
- Publication date: 2024/10
- DOI: http://dx.doi.org/10.1016/j.ijrefrig.2024.06.025
Links
See other articles in this issue (20)
See the source
Indexing
-
Ignition sources at the stage of usage for mini...
- Author(s) : TAMURA K., TAKAICHI K., TAIRA S., BABA A., ITAKURA S., MORI H., MAKINO H.
- Date : 2020/12/07
- Languages : English
- Source: 14th IIR-Gustav Lorentzen Conference on Natural Refrigerants (GL2020). Proceedings. Kyoto, Japon, December 7-9th 2020.
- Formats : PDF
View record
-
CFD analysis of propane dispersion in an indoor...
- Author(s) : RIGHETTI G., CALATI M., LONGO G. A., MANCIN S., ZILIO C.
- Date : 2021/09/01
- Languages : English
- Source: 6th IIR Conference on Thermophysical Properties and Transfer Processes of Refrigerants
- Formats : PDF
View record
-
Indoor leakage test for safety of R-290 split t...
- Author(s) : LI T.
- Date : 2014/04
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 40
- Formats : PDF
View record
-
Refrigerant concentration mapping using real-ti...
- Author(s) : MEDINA J., KOBAN M.
- Date : 2021/05
- Languages : English
- Source: 2021 Purdue Conferences. 18th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
View record
-
A3 Refrigerant R290 Leak and Ignition Testing f...
- Author(s) : WANG H., HUNTER G.
- Date : 2021/08/31
- Languages : English
- Source: 13th IEA Heat Pump Conference 2021: Heat Pumps – Mission for the Green World. Conference proceedings [full papers]
- Formats : PDF
View record