IIR document

Two-phase split of refrigerants at a T-junction.

Author(s) : TAE S. J., CHO K.

Type of article: Article, IJR article

Summary

The present study experimentally investigated the two-phase flow split of refrigerants at a T-junction. As geometric parameters, the direction of the inlet or branch tube and the tube diameter ratio of branch to inlet tube were chosen. As inlet flow parameters, the inlet mass flux and quality were varied from 100 to 700 kg/m2.s and from 0.1 to 0.9, respectively, for the condition of distribution header of a multi-pass evaporator in the general refrigeration system. All experiments were performed for R22, R134a, and R410A. The measured data were compared with the values predicted by the models developed for air-water or steam-water mixture in the literature. The authors propose a modified model for application to the reduced T-junction and vertical orientation of tubes. Among the geometric parameters, the branch tube direction showed the largest sensitivity to the mass flow rate ratio for the gas phase, while the inlet quality showed the largest sensitivity to the mass flow rate ratio among the inlet flow parameters.

Available documents

Format PDF

Pages: 1128-1137

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Two-phase split of refrigerants at a T-junction.
  • Record ID : 2006-2202
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 29 - n. 7
  • Publication date: 2006/11

Links


See other articles in this issue (18)
See the source