Viscosities for R22 alternatives and their mixtures with a lubricant oil.

Summary

Viscosities for pure liquid refrigerants R32, R125, R134a, and R143a, as well as their mixtures with a synthetic polyolester lubricant oil, have been measured. Measurements for the refrigerant-lubricant mixtures were made over a temperature range from 20 to 80 deg C and a range of oil mass fractions from 0.5 to 1. A modified capillary tube method was used for all measurements. The accuracy of measured viscosities is estimated to be more or less 1.2% and more or less 1.8% for pure refrigerants and for refrigerant-oil mixtures, respectively. Correlations for calculating the viscosity of saturated liquid refrigerants were developed. A method has also been proposed to calculate viscosities of refrigerant-oil mixtures on the basis of pure component data alone.

Available documents

Format PDF

Pages: 49-54

Available

  • Public price

    20 €

  • Member price*

    15 €

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Viscosities for R22 alternatives and their mixtures with a lubricant oil.
  • Record ID : 1995-0739
  • Languages: English
  • Source: Proceedings of the 1994 International Refrigeration Conference at Purdue.
  • Publication date: 1994/07/19

Links


See other articles from the proceedings (73)
See the conference proceedings