Refrigerant/oil interaction in HFC/ester oil systems: effects on thermodynamics and refrigerating capacity.

Kältemittel/Kältemaschinenöl-Wechselwirkungen in HFKW/Esteröl-Systemem: Auswirkung auf Thermodynamik und Anlagenleistung.

Summary

The paper reports on the effect of refrigerating machine oils on thermodynamic properties and performance in the circuits of commercially available HFC blends. Azeotropic, near-azeotropic and zeotropic binary and ternary blends from R32, R143a, R125 and R134a, in combination with an ISO-VG32 polyolester, were considered. Calculations show that oil proportions of 1-2% can influence refrigerating performance, compression enthalpy and COP.

Details

  • Original title: Kältemittel/Kältemaschinenöl-Wechselwirkungen in HFKW/Esteröl-Systemem: Auswirkung auf Thermodynamik und Anlagenleistung.
  • Record ID : 1998-0108
  • Languages: German
  • Source: DKV-Tagungsbericht 23. 1996 Leipzig.
  • Publication date: 1996/11/20
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles from the proceedings (54)
See the conference proceedings