IIR document

Experimental tests using deactivation of coolant fluid circulation to mitigate frost formation on the heat exchanger surface.

Number: pap. n. 989

Author(s) : PANOIAS P., SILVA P. D., PIRES L., et al.

Summary

The use of cold for conservation of food products requires large consumption of electricity. In order to obtain lower temperatures than those available in the same space, the evaporator coils, generally operate at temperatures lower than the freezing point of the water. The ice formed on the surface is detrimental both to the thermal and the energetic level of the refrigeration system. Thus, ice removal is critical to reestablish the desired operating conditions. This paper presents a refrigeration apparatus setup composed by two heat exchangers connected in parallel. The coolant fluid circulation is deactivated during short periods of operation, and the ice formation on the coil surface is analyzed. The results show that this strategic deactivation of coolant fluid circulation proved to be a viable operating condition since allowed an extension of the refrigeration system operation with a stable cooling power and so better thermal efficiency.

Available documents

Format PDF

Pages: 7

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Experimental tests using deactivation of coolant fluid circulation to mitigate frost formation on the heat exchanger surface.
  • Record ID : 30026685
  • Languages: English
  • Source: Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
  • Publication date: 2019/08/24
  • DOI: http://dx.doi.org/10.18462/iir.icr.2019.0989
  • Notes:

    Keynote


Links


See other articles from the proceedings (632)
See the conference proceedings