Summary
For a space heating air source heat pump (ASHP) unit, when its outdoor coil surface temperature is below both the air dew point temperature and the freezing point of water, frost will form on its outdoor coil surface. Frosting affects its operational performance and energy efficiency. Therefore, periodic defrosting is necessary. Currently, the most widely used standard defrosting method for ASHP units is reverse cycle defrost. The energy that should have been used for space heating is used to melt frost, vaporize the melted frost off outdoor coil surface and heat ambient air during defrosting. It is therefore necessary to study the sources of heat supplies and the end-uses of the heat supplied during a reverse cycle defrost operation. In this paper, firstly, an experimental setup is described and experimental procedures are detailed. This is followed by reporting the experimental results and the evaluation of defrosting efficiency for the experimental ASHP unit. Finally, an evaluation of defrosting heat supplies and energy consumptions during a revere cycle defrost operation for the experimental ASHP unit is presented. The experimental and evaluation results indicated that the heat supply from indoor air contributed to 71.8% of the total heat supplied for defrosting and 59.4% of the supplied energy was used for melting frost. The maximum defrosting efficiency could be up to 60.1%. [Reprinted with permission of Elsevier. Copyright 2012.]
Details
- Original title: An experimental study on defrosting heat supplies and energy consumptions during a reverse cycle defrost operation for an air source heat pump.
- Record ID : 30003703
- Languages: English
- Source: Applied Thermal Engineering - vol. 37
- Publication date: 2012/05
- DOI: http://dx.doi.org/10.1016/j.applthermaleng.2011.11.052
Links
See other articles in this issue (9)
See the source
Indexing
-
Themes:
Heat pumps techniques;
Defrosting systems - Keywords: Heat; Energy consumption; Air; Heat pump; Expérimentation; Defrosting
-
Experimental study of the characteristic of com...
- Author(s) : LIN H., NAN J., QIAO M., et al.
- Date : 2017/02
- Languages : Chinese
- Source: Journal of Refrigeration - vol. 38 - n. 1
- Formats : PDF
View record
-
An experimental study of defrosting energy of a...
- Author(s) : ZHANG W., HRNJAK P.
- Date : 2022/07/10
- Languages : English
- Source: 2022 Purdue Conferences. 19th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
View record
-
Defrosting of air coolers in refrigerating appl...
- Author(s) : ZAKRZEWSKI B., LOKIETEK T., HRYCYK E.
- Date : 2011/08/21
- Languages : English
- Source: Proceedings of the 23rd IIR International Congress of Refrigeration: Prague, Czech Republic, August 21-26, 2011. Overarching theme: Refrigeration for Sustainable Development.
- Formats : PDF
View record
-
Systemy odszraniania powietrznych pomp ciepla.
- Date : 2008
- Languages : Polish
- Source: Chlodnictwo - vol. 43 - n. 10
View record
-
Study on the defrosting control method based on...
- Author(s) : XING Z., GUO X., LI J.
- Date : 2016/06
- Languages : Chinese
- Source: Journal of Refrigeration - vol. 37 - n. 169
- Formats : PDF
View record