Experiment on a novel defrost cycle for air source heat pumps.

[In Chinese. / En chinois.]

Author(s) : FU W., GUO X., TAO X.

Type of article: Article

Summary

On the basis of the hot gas bypass defrost cycle, a new defrost method for air-source heat pumps was proposed. In the present defrost cycle, the outdoor heat exchanger is divided into two parts connected by a capillary tube. The front part and the rear part of the heat exchanger are used as an evaporator and a condenser respectively during the defrost process, and the defrost is completed by a four-way valve. The defrost performance of the new cycle was investigated experimentally and compared with that of a reverse-cycle defrost system. The experimental results indicate that the energy was used more efficiently, and thus the defrost time and the defrost loss of the new cycle were less than those of the reverse-cycle defrost system. Moreover, heat was not extracted from the indoor space during the defrost process. The switch time of the four-way valve in the new defrost system was the same to that of the reverse-cycle defrost system, and the fluctuation of the discharge and suction pressures during the defrost process was much less than that in the reverse-cycle defrost cycle.

Available documents

Format PDF

Pages: pp. 16-21

Available

  • Public price

    20 €

  • Member price*

    15 €

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details


Links


See other articles in this issue (4)
See the source