Analysis of segment-by-segment epsilon-NTU modelling of a minichannel CO2 gas cooler.

Summary

Most of the current air-to-refrigerant heat exchanger models use the classic epsilon-NTU approach. These models do not account for longitudinal conduction neither in the fin nor in the tube, transverse conduction in the tube, and for the heat conduction between different tubes, which is a consequence of the employed adiabatic fin tip assumption. This paper presents a more detailed numerical approach to heat exchanger modelling with the goal to capture heat conduction effects within the heat exchanger structure and detailed representation of air properties. The new model uses a segment-by-segment approach and applies a 2-D discretization for each segment. The paper includes a presentation of the numerical scheme, validation, and a parametric study which tests the impact of the traditional heat exchanger model assumptions. The study revealed large errors in capacity prediction of individual tubes due to the adiabatic fin tip assumption, when the neighbouring tubes are of different temperature.

Available documents

Format PDF

Available

  • Public price

    20 €

  • Member price*

    15 €

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Analysis of segment-by-segment epsilon-NTU modelling of a minichannel CO2 gas cooler.
  • Record ID : 2010-1797
  • Languages: English
  • Publication date: 2010/07/12
  • Source: Source: Proc. 2010 int. Refrig. Air Cond. Conf., Purdue Univ.
    n. 2169; 8 p.; fig.; tabl.; 13 ref.