IIR document

Cycle analysis and heat transfer characteristics of a heat pump using R22-R142b refrigerant mixtures.

Author(s) : KIM T. S., SHIN J. Y., KIM M. S., RO S. T.

Type of article: Article, IJR article

Summary

Heat transfer coefficient in the evaporator and overall performance are measured and analysed in terms of compositions and relevant variables. The possibility is observed of capacity modulation within 200% (based on minimum capacity) by varying the composition without degradation of heat transfer effectiveness and COP. At a fixed evaporating capacity, COP is improved by using refrigerant mixtures, and shows its maximum at 60% mass fraction of R22. Local heat transfer coefficients are measured in the evaporator. At similar mass flow rate and evaporating heat transfer rate, the average heat transfer coefficients for mixtures are lower than those for pure refrigerants.

Available documents

Format PDF

Pages: 391-399

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Cycle analysis and heat transfer characteristics of a heat pump using R22-R142b refrigerant mixtures.
  • Record ID : 1995-1125
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 17 - n. 6
  • Publication date: 1994/07