DEVELOPMENT OF A HEAT PUMP HEATING, COOLING AND HOT WATER-GENERATING SYSTEM WITH REFRIGERANT MIXTURE.

Author(s) : TANAKA N.

Summary

THE HEATING, COOLING, AND GENERATION OF 358 K (85 DEG C) HOT WATER COULD BE DONE EFFICIENTLY. THE IDEA IS TO ADAPT A HIGH PRESSURE REFRIGERANT FOR HEATING, COOLING, AND LOW-TEMPERATURE HOT WATER GENERATION, WHILE THE REFRIGERANT MIXTURE (LOW PRESSURE) IS USED FOR HIGH-TEMPERATURE HOT WATER GENERATION. ITS PRACTICAL APPLICATION REQUIRES MIXING AND SEPARATING OPERATIONS BEFORE AND AFTER THE HIGH-TEMPERATURE HOT WATER GENERATION. PRELIMINARY EXPERIMENTS WITH AN R22/R114 MIXTURE CONFIRMED THAT A SMALL PACKED TOWER COULD RECTIFY THE REFRIGERANT OF THE MAIN CIRCUIT IN A SHORT TIME. A PRACTICAL SYSTEM WAS DEVELOPED AND TESTED. THE RESULTS SHOWED EXCELLENT PERFORMANCE FOR EACH OPERATING MODE.

Details

  • Original title: DEVELOPMENT OF A HEAT PUMP HEATING, COOLING AND HOT WATER-GENERATING SYSTEM WITH REFRIGERANT MIXTURE.
  • Record ID : 1988-0332
  • Languages: English
  • Publication date: 1987
  • Source: Source: ASHRAE Trans.
    vol. 93; n. 1; 601-614; 8 fig.; 8 tabl.; 1 ref.