Minimum airflow rates to dilute A2L refrigerant leaks from refrigeration systems.

Number: pap. n. 1189

Author(s) : COLBOURNE D., SUEN K. O.

Summary

As part of the work under International Electrotechnical Commission (IEC) SC 61D for safety of air conditioners, rules for extending charge of A2 and A3 refrigerants (with respect to room size) are under development within the working group, WG16. Requirements have evolved to utilise airflow from indoor units (IDUs) to dilute any possible leak of flammable refrigerant. Research has been carried out to determine the minimum airflow rate necessary to achieve sufficient dilution of the flammable mixtures and a numerical model based on entrainment theory was developed and previously validated for A3 refrigerants. New IEC 60335-2-40: 2018 which includes revisions specifically for A2Ls contains rules for determining IDU airflow requirements but were not validated and in several respects are contradictory. Therefore the method developed for A2 and A3 refrigerants under WG16 need to be assessed with respect to extending its application to A2L refrigerants.

Available documents

Format PDF

Pages: 11

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Minimum airflow rates to dilute A2L refrigerant leaks from refrigeration systems.
  • Record ID : 30024881
  • Languages: English
  • Source: 1st IIR international conference on the application of HFO refrigerants, Birmingham, September 2-5 2018.
  • Publication date: 2018/09
  • DOI: http://dx.doi.org/10.18462/iir.hfo.2018.1189

Links


See other articles from the proceedings (126)
See the conference proceedings