Nucleate boiling heat transfer of R134a on enhanced tubes.
Author(s) : RIBATSKI G., THOME J. R.
Type of article: Article
Summary
The present paper reports the results of an experimental investigation on saturated pool boiling heat transfer of R134a on High-Flux, Gewa-B, Turbo-CSL and Turbo-BII HP tubes. Experiments have been carried out at saturation temperatures of 5, 10 and 20°C and heat fluxes from 20 to 70 kW/m2. At most of the experimental conditions tested, an almost negligible effect of the saturation temperature on the heat transfer coefficient was found. Except for Turbo-CSL, the heat transfer coefficient presented either a slight decrease in its value or an almost constant value with increasing heat flux. The heat transfer enhancement ratios of the High-Flux, Gewa-B, Turbo-CSL and Turbo-BII HP tubes were 4.9-21.3, 2.4-5.2, 2.4-2.9 and 1.8-7.0, respectively, compared to a plain tube. [Reprinted with permission from Elsevier. Copyright, 2005].
Details
- Original title: Nucleate boiling heat transfer of R134a on enhanced tubes.
- Record ID : 2006-1642
- Languages: English
- Source: Applied Thermal Engineering - vol. 26 - n. 10
- Publication date: 2006/07
Links
See other articles in this issue (4)
See the source
Indexing
-
Themes:
HFCs;
Heat transfer;
Mass transfer - Keywords: R134a; Pool boiling; Horizontal tube; Extended surface; Heat transfer; Expérimentation; Refrigerant; Nucleate boiling
-
LDV assisted bubble dynamic parameter measureme...
- Author(s) : HSIEH S. S., LAI W. C., TSAI H. H.
- Date : 2003/12
- Languages : English
- Source: International Journal of Heat and Mass Transfer - vol. 46 - n. 25
View record
-
Heat transfer and bubble formation in pool boil...
- Author(s) : KOTTHOFF S., GORENFLO D., DANGER E., et al.
- Date : 2006/03
- Languages : English
- Source: International Journal of thermal Sciences - vol. 45 - n. 3
View record
-
Pool-boiling heat transfer from horizontal tube...
- Author(s) : GORENFLO D.
- Date : 1993/12/06
- Languages : English
- Source: Proceedings of international seminar on heat transfer, thermophysical properties and cycle performance of alternative refrigerants.
View record
-
POOL BOILING DATA FOR FIVE REFRIGERANTS ON THRE...
- Author(s) : WEBB R. L., PAIS C.
- Date : 1991
- Languages : English
View record
-
A correlation of forced convective boiling heat...
- Author(s) : MOMOKI S., YU J., KOYAMA S., FUJII T., HONDA H.
- Date : 1995
- Languages : Japanese
- Source: Trans. JAR - vol. 12 - n. 2