IIR document

Numerical-based non-dimensional analysis of critical flow of R-12, R-22, and R-134a through horizontal capillary tubes.

Author(s) : JAVIDMAND P., HOFFMANN K. A.

Type of article: Article, IJR article

Summary

Development of correlations predicting critical mass flow rate and critical pressure distribution through capillary tubes is presented. In order to accomplish such a work, the critical mass flow rate and pressure distribution for nearly 500 operational conditions for R-12, R-22, and R-134a are evaluated. Operational conditions include inlet pressure varying from 800 to 1500 kPa, inlet subcold temperature between 0 and 10°C, length varying from 1 to 2 m, and inner diameter between 0.5 and 1.5 mm. By performing non-dimensional analysis on numerical data, general correlations are presented to predict the critical mass flow rate through capillary tubes. In addition, by utilizing numerical data for down-stream pressure, non-dimensional analysis is performed to present correlations to predict critical down-stream pressure and pressure distribution through capillary tubes.

Available documents

Format PDF

Pages: 58-68

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Numerical-based non-dimensional analysis of critical flow of R-12, R-22, and R-134a through horizontal capillary tubes.
  • Record ID : 30015668
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 58
  • Publication date: 2015/10

Links


See other articles in this issue (23)
See the source