IIR document

Performance characteristics of vapour-compression refrigeration cycle based on the Ericsson cycle.

Author(s) : INO N., KISHI T., NISHIO T., et al.

Summary

The purpose of this research and investigation is to confirm and clarify the performance characteristics of the vapour-compression refrigerating cycle based on the Ericsson cycle. The theoretical analysis and comparison in performance of the conventional refrigerating cycle with this cycle using 12 different but typical refrigerants, produced the following essential and interesting results, i.e., there are conditions for maximizing the COP of this cycle using the expansion valve, which are decided by the dryness fraction of the inlet gas at a regenerative heat exchanger, both the COP and refrigerating capacity using this cycle show improvement for all refrigerants other than R-717 and R-32, the operational stability of this cycle is excellent against unsteady operating conditions such as refrigerant liquid flow back to a compressor.

Available documents

Format PDF

Pages: ICR07-B1-164

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Performance characteristics of vapour-compression refrigeration cycle based on the Ericsson cycle.
  • Record ID : 2007-2542
  • Languages: English
  • Source: ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
  • Publication date: 2007/08/21