SINGLE-STAGE RECUPERATOR CYCLE FOR PRODUCING LOW TEMPERATURES WITH REFRIGERANT MIXTURES.
[In German. / En allemand.]
Author(s) : GROMOLL B.
Type of article: Article
Summary
WITH THE RECUPERATOR CYCLE CERTAIN PROPERTIES OF NON-AZEOTROPIC REFRIGERANT MIXTURES ARE UTILIZED TO PRODUCE LOW TEMPERATURES IN A SIMPLE MANNER. SINGLE-STAGE COMPRESSION SUFFICES HERE TO OBTAIN TEMPERATURES WHICH, WITH CONVENTIONAL METHODS, WOULD REQUIRE COMPLEX PROCESSES. STANDARD REFRIGERATION COMPONENTS WERE ASSEMBLED TO FORM A SINGLE-STAGE UNIT IN A RECUPERATOR CONNECTION. IT WAS USED TO INVESTIGATE A TOTAL OF 30 DIFFERENT REFRIGERANT MIXTURES. REGARDING THE COP AND REFRIGERATING CAPACITY, GOOD RESULTS WERE OBTAINED FOR R502-R13 AND R12-R13 MIXTURES AT TEMPERATURES DOWN TO 203K (-70 DEG C). MIXTURES OF R502-R14 ARE SUITABLE FOR TEMPERATURES DOWN TO 183 K (-90 DEG C) AND OF R12-R14 FOR TEMPERATURES DOWN TO 163 K (-110 DEG C).
Details
- Original title: [In German. / En allemand.]
- Record ID : 1990-2275
- Languages: German
- Source: Klima Kälte Heiz. - vol. 17 - n. 11
- Publication date: 1989
- Document available for consultation in the library of the IIR headquarters only.
Links
See other articles in this issue (3)
See the source
Indexing
-
Themes:
CFCs;
Hydrocarbons;
Other refrigerants;
Blends;
Containment, refrigerant charge reduction - Keywords: R14; Recovery; R502; R13; R12; Zeotropic mixture; Refrigerant
-
RECOVERING CHLOROFLUOROCARBONS.
- Author(s) : BISIO G., RUBATTO G.
- Date : 1990
- Languages : Italian
- Source: Industria italiana del Freddo - vol. 44 - n. 3
View record
-
THERMAL CONDUCTIVITY OF BINARY MIXTURES OF THE ...
- Author(s) : CVETKOV O. B.
- Date : 1985
- Languages : Russian
- Source: Kholodilnaya Tekhnika - n. 7
View record
-
The use of mixtures in refrigerating plants.
- Author(s) : CAMPAGNA E.
- Date : 1995/06/16
- Languages : Italian
- Source: I nuovi refrigeranti ed il settore alimentare. Le ultime tecnologie e il futuro del freddo e del condizionamento. / The new refrigerants and the food industry.The future of refrigeration and air conditioning.
View record
-
INTERACTION PARAMETER, K12 , FOR NON-AZEOTROPIC...
- Author(s) : CAMPORESE R., BIGOLARO G., MURASCKIN A.
- Date : 1985
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 8 - n. 5
- Formats : PDF
View record
-
RECOVERY OF CFC REFRIGERANTS DURING SERVICE AND...
- Author(s) : MANZ K. W.
- Date : 1988
- Languages : English
View record