IIR document

Supercooling of water in commercial-sized evaporator tubes with internal fins.

La surfusion de l'eau dans des tubes d'évaporateur de dimensions commerciales avec ailettes intérieures.

Summary

A study was done of the new technology capable of generating flows of supercooled water. An experimental study was carried out in order to check if the phenomenon of supercooling could be inhibited by the presence of fins inside tubes having an internal diameter of 15.7mm. During tests, the Reynolds number of the water flow varied from 3,400 to 29,900, with an inlet temperature of between 0.2 and 6.1 deg C. Even with an outlet water temperature of -3 deg C, the presence of internal fins causes no inhibition of the supercooling phenomenon and helps increase heat flow.

Available documents

Format PDF

Pages: 171-177

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: La surfusion de l'eau dans des tubes d'évaporateur de dimensions commerciales avec ailettes intérieures.
  • Record ID : 1996-2119
  • Languages: French
  • Source: For a Better Quality of Life. 19th International Congress of Refrigeration.
  • Publication date: 1995/08/20