Temperature-heat diagram analysis method for multi-stage heat regeneration physical adsorption refrigeration cycle.
Number: pap. n. 425
Author(s) : XU S. Z., WANG L. W., WANG R. Z.
Summary
The method of temperature–heat (T–Q )diagram analysis was proposed in this paper. In T–Q diagram, the area between two process curves along the temperature axis represents the irreversibility degree in the heat transfer process, which has the same dimension with entransy dissipation. The diagram can be used to optimize the heat exchange configuration and the heat exchanger network of an adsorption refrigeration system. The proposed T–Q diagram and the traditional COP, exergy and entropy analysis were adopted to a multi-stage heat regenerative adsorption chiller under different heat regeneration schemes. The results show that the optimal scheme determined through T–Q diagram and cycle entropy production analysis are identical, while T–Q diagram is more intuitional since the analysis is done graphically. If consider a complete heat regeneration between two adsorption beds, the performance of the multi-stage chiller with different heat regeneration schemes should be almost the same.
Available documents
Format PDF
Pages: 8 p.
Available
Public price
20 €
Member price*
Free
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: Temperature-heat diagram analysis method for multi-stage heat regeneration physical adsorption refrigeration cycle.
- Record ID : 30015842
- Languages: English
- Source: Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
- Publication date: 2015/08/16
- DOI: http://dx.doi.org/10.18462/iir.icr.2015.0425
Links
See other articles from the proceedings (657)
See the conference proceedings
-
The cycle time optimization of a novel dual eva...
- Author(s) : MIYAZAKI T., UEDA Y., AKISAWA A., et al.
- Date : 2010/06/07
- Languages : English
- Source: ACRA2010. Asian conference on refrigeration and air conditioning: Tokyo, Japan, June 7-9, 2010.
- Formats : PDF
View record
-
Simulation of fluid flow characteristics of mul...
- Author(s) : ZHU C., XIE X., JIANG Y.
- Date : 2014/03/02
- Languages : English
- Source: International sorption heat pump conference (ISHPC2014), College Park, United States, March 31-April 2, 2014.
- Formats : PDF
View record
-
Performance analysis of adsorption refrigeratio...
- Author(s) : CHANG Y. C., KIM T. H., KANG B. H.
- Date : 2017/08/07
- Languages : English
- Source: International sorption heat pump conference, ISHPC 2017, Tokyo august 7-10.
View record
-
A novel criterion to evaluate the temperature m...
- Author(s) : WANG H. T., WANG H., GE Z.
- Date : 2010/12/18
- Languages : English
View record
-
Analysis of droplet motion - sliding on and det...
- Author(s) : ZOU H., JIN H., WANG S.
- Date : 2022
- Languages : English
- Source: 2022 Purdue Conferences. 19th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
View record