The effect of energy recovery on perceived air quality, energy consumption, and the economics of an office building.
Author(s) : FAUCHOUX M. T., SIMONSON C. J., TORVI D. A.
Summary
The objectives of this paper are to determine if an energy wheel can improve indoor air relative humidity (RH) and perceived air quality (PAQ), as well as reduce energy consumption. The TRNSYS computer package is used to model an office building in four North American cities (Saskatoon, Saskatchewan; Vancouver, British Columbia; Tampa, Florida; and Phoenix, Arizona). The results with and without an energy wheel are compared to see if the energy wheel has a significant impact on the RH and PAQ in the building. The energy wheel significantly reduces peak RH levels in Tampa and Phoenix and has a smaller effect in Saskatoon. The energy wheel reduces the number of people that are dissatisfied with the PAQ within the space in these cities. By using an energy wheel, the total energy consumed by the HVAC system in Saskatoon, Phoenix, and Tampa is reduced. There is a significant reduction in the size of the heating equipment in Saskatoon and in the size of the cooling equipment in Phoenix and Tampa. A cost analysis shows that the HVAC system including an energy wheel has the least life-cycle costs in these three cities. In Vancouver, the energy wheel has a negligible impact on the indoor RH, PAQ, energy consumption, and life-cycle cost.
Details
- Original title: The effect of energy recovery on perceived air quality, energy consumption, and the economics of an office building.
- Record ID : 2008-1755
- Languages: English
- Source: ASHRAE Transactions. 2007 Annual Meeting, Long Beach, CA. Volume 113, part 2 + CD-ROM.
- Publication date: 2007/06/23
Links
See other articles from the proceedings (22)
See the conference proceedings
Indexing
- Themes: Indoor air quality
- Keywords: Office; Energy consumption; Building; Air quality; Simulation; Thermal wheel; Relative humidity; Air conditioning
-
INTERRELATIONSHIPS BETWEEN TEMPERATURE AND HUMI...
- Author(s) : BERGLUND L. G., SUPPAN P.
- Date : 1989/08/01
- Languages : English
View record
-
FIELD STUDY ON INDOOR AIR QUALITY OF BODY ODOUR...
- Author(s) : IWASHITA G.
- Date : 1989/08/01
- Languages : English
View record
-
Air quality in German office buildings.
- Author(s) : FINKE U., FITZNER K.
- Date : 1994/11/16
- Languages : German
- Source: DKV-Tagungsbericht 1994 Bonn.
View record
-
Indoor air quality and thermal comfort studies ...
- Author(s) : HAGHIGHAT F., DONNINI G.
- Date : 1997/09/09
- Languages : English
- Source: International Symposium on Air Conditioning in High Rise Buildings - 1997
- Formats : PDF
View record
-
Lohnt es sich in ein gutes Raumklima zu investi...
- Author(s) : OLESEN B. W.
- Date : 2005/11/16
- Languages : German
- Source: DKV-Tagungsbericht 2005, Würzburg./ 2005 Proceedings of the DKV Conference, Würzburg.
View record