IIR document

THE EFFECT OF VAPOUR CONDENSATION ON THE SENSIBLE HEAT TRANSFER COEFFICIENT IN FINNED COIL AIR COOLERS.

Summary

THE AUTHORS DEVELOPED A PROGRAMME FORTHE DETERMINATION OF THE HEAT TRANSFER COEFFICIENT ON THE AIR SIDE IN FINNED TUBE HEAT EXCHANGERS. THIS PROGRAMME USES A SERIES OF TEST RESULTS SHOWING THAT THE VALUE OF THE COEFFICIENT SLIGHTLY INCREASES WHEN THERE IS CONDENSATION ON THE FIN SURFACE ; THIS VALUE DOES NOT DEPEND ON LATENT HEAT FLOW, BUT ONLY ON AIR VELOCITY. THE AUTHORS TESTED AN EXCHANGER WITH FINS SUBJECTED TO A SURFACE TREATMENT PROVIDING FILM CONDENSATION. THEY OBTAINED A MARKED DECREASE IN THE AIR PRESSURE DROP.

Available documents

Format PDF

Pages: vol. B-E

This document is to be digitised and will be available within 10 working days

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: THE EFFECT OF VAPOUR CONDENSATION ON THE SENSIBLE HEAT TRANSFER COEFFICIENT IN FINNED COIL AIR COOLERS.
  • Record ID : 1988-1797
  • Languages: English
  • Source: Development in refrigeration, refrigeration for development. Proceedings of the XVIIth international Congress of Refrigeration.
  • Publication date: 1987/08/24
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles from the proceedings (509)
See the conference proceedings