IIR document

Theoretical and experimental analysis of an absorption chiller.

Author(s) : NG K. C., BONG T. Y., CHUA H. T., BAO H. L.

Type of article: Article, IJR article

Summary

An experimental investigation was conducted to validate a theoretical model using a single-stage, water-lithium bromide absorption chiller of 2 t rated capacity. The tests were conducted in a water-cooled chiller testing facility, which does not require any external heating or cooling. Instead, it employs a mixing tank that neutralizes the heating effect of the condenser-absorber with that of the cooling effect of the evaporator, and the remaining excess heat is rejected through a cooling tower. The experimental results and the manufacturer's data for the test unit both indicate a linear relationship for the proposed parameter. The cooling capacities obtained from the test unit are consistently lower than the manufacturer's by about 10-25%.

Available documents

Format PDF

Pages: 351-358

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Theoretical and experimental analysis of an absorption chiller.
  • Record ID : 1995-2215
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 17 - n. 5
  • Publication date: 1994/06

Links


See other articles in this issue (7)
See the source