THERMODYNAMIC DESIGN DATA FOR ABSORPTION HEAT TRANSFORMERS. 2. OPERATING ON WATER-CALCIUM CHLORIDE.

Author(s) : EISA M. A. R., BEST R., HOLLAND F. A.

Type of article: Article

Summary

THE GIBBS PHASE RULE AND THE THERMODYNAMIC PROPERTIES OF THE WORKING PAIR LIMIT THE CHOICE OF OPERATING TEMPERATURES. FOR ANY COMBINATION OF TEMPERATURES, THE CONCENTRATIONS IN THE ABSORBER AND THE GENERATOR AND THE FLOW RATIOS ARE FIXED. FOR ANY PARTICULAR WORKING PAIR, THE COP IS RELATED TO THE FLOW RATIO. TABLES OF POSSIBLE COMBINATIONS OF OPERATING TEMPERATURES AND CONCENTRATIONS, INCLUDING FLOW RATIOS, CARNOT COP AND ENTHALPY BASED COP HAVE BEEN PRESENTED FOR HEAT TRANSFORMERS OPERATING ON WATER-CALCIUM CHLORIDE.

Details

  • Original title: THERMODYNAMIC DESIGN DATA FOR ABSORPTION HEAT TRANSFORMERS. 2. OPERATING ON WATER-CALCIUM CHLORIDE.
  • Record ID : 1987-2392
  • Languages: English
  • Source: J. Heat Recov. Syst. - vol. 6 - n. 6
  • Publication date: 1986
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles in this issue (6)