Experimental evaluation of HCFC-22 replacement by the drop-in fluids HFC-422A and HFC-417B for low temperature refrigeration applications.
Author(s) : LLOPIS R., CABELLO R., SÁNCHEZ D., et al.
Type of article: Article
Summary
The Regulation CE-1005/2009 has banned the use of virgin HCFC-22 in Europe from the 31st December 2009, because it contains chlorine, although its use is allowed up to the 31st December 2014 if it is recycled. Now, manufacturers are developing different free-chlorine drop-in solutions to replace the HCFC-22 in the existing equipment by non-ozone depleting substances in order to exhaust its remaining life. This work focuses on the experimental evaluation of two HCFC-22 drop-in solutions for low temperature applications, the HFC-422A and the HFC-417B, in a double-stage vapour compression plant driven by a compound compressor in an evaporating temperature range between -31 and -17 °C and in a condensing temperature range between 30 and 48 °C. The experimental results show that there is a reduction in cooling capacity and in COP with regard to the HCFC-22 operation, which is analysed and discussed in the paper. [Reprinted with permission of Elsevier. Copyright 2011.]
Details
- Original title: Experimental evaluation of HCFC-22 replacement by the drop-in fluids HFC-422A and HFC-417B for low temperature refrigeration applications.
- Record ID : 30003692
- Languages: English
- Source: Applied Thermal Engineering - vol. 31 - n.6-7
- Publication date: 2011/05
- DOI: http://dx.doi.org/10.1016/j.applthermaleng.2011.01.003
Links
See other articles in this issue (11)
See the source
Indexing
-
Themes:
Compression systems;
HCFCs;
HFCs;
Hydrocarbons;
Blends - Keywords: R422a; Low temperature; Drop-in; R22; Two-stage system; Substitute; Expérimentation; Refrigerant
-
Replacement of HCFC-22 refrigerant with a drop-...
- Author(s) : LLOPIS R., CABELLO R., SÁNCHEZ D., et al.
- Date : 2012/02/22
- Languages : English
- Source: CYTEF 2012. VI Congreso Ibérico y IV Congreso Iberoamericano de Ciencias y Técnicas del Frío, Madrid, España, 22-24 de febrero, 2012.
- Formats : PDF
View record
-
HCFC-22 replacement with HFC drop-in refrigeran...
- Author(s) : LLOPIS R., TORRELLA E., CABELLO R., et al.
- Date : 2011/08/21
- Languages : English
- Source: Proceedings of the 23rd IIR International Congress of Refrigeration: Prague, Czech Republic, August 21-26, 2011. Overarching theme: Refrigeration for Sustainable Development.
- Formats : PDF
View record
-
Fluidi refrigeranti in sostituzione all'R22.
- Author(s) : CAMPAGNA E.
- Date : 2012/07
- Languages : Italian
- Source: Industria & Formazione - vol. 36 - n. 361
- Formats : PDF
View record
-
HCFC-22 replacement with drop-in and retrofit H...
- Author(s) : LLOPIS R., TORRELLA E., CABELLO R., et al.
- Date : 2012/06
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 35 - n. 4
- Formats : PDF
View record
-
R22 drop-in, a success at the Building Research...
- Author(s) : BUTLER D.
- Date : 1994/09
- Languages : English
View record