IIR document

Compact ejector optimised compressor pack for carbon dioxide.

Number: 0800

Author(s) : HEERUP C., LARSEN L. F. S., MADSEN K. B.

Summary

The present work investigates the impact of an ejector module on the performance of a CO2 compressor pack for supermarket applications. The European ecodesign criteria for condensing units were used as a framework to test and assess the performance of the system with and without active ejector, in terms of both capacity and energy efficiency. Seasonal energy performance ratio calculations were used to compare the test results. Results showed that at high ambient temperature the ejector increases the system capacity and efficiency by up to 34% and 24% respectively, thus enabling the downsizing of the compressor pack. However, the seasonal efficiency improvement was less than 5% at conditions corresponding to Northern Europe. Conditions corresponding to a high heat recovery demand in winter were also evaluated, which showed an increase in seasonal heating efficiency of up to 21%.

Available documents

Format PDF

Pages: 11

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Compact ejector optimised compressor pack for carbon dioxide.
  • Record ID : 30031840
  • Languages: English
  • Subject: Technology
  • Source: Proceedings of the 26th IIR International Congress of Refrigeration: Paris , France, August 21-25, 2023.
  • Publication date: 2023/08/21
  • DOI: http://dx.doi.org/10.18462/iir.icr.2023.0800