Comparison of compressor efficiency between rotary and scroll type with alternative refrigerants for R22.
Author(s) : KATO T., SHIRAFUJI Y., KAWAGUCHI S.
Summary
The efficiency of compressors optimized for each refrigerant is theoretically figured out, and it is also experimentally confirmed. As the results, the upper limit of cooling capacity range, in which efficiency of rotary type is higher than that of scroll type, is about 2,344 watt with R22 and R407C. In the case with R410A, rotary type is superior to scroll type in the range approximately up to 7,032 watt. The study shows that the range in which rotary types operates more efficiently than scroll type will expand up to small capacity range of unitary air conditioners in the case with R410A.
Details
- Original title: Comparison of compressor efficiency between rotary and scroll type with alternative refrigerants for R22.
- Record ID : 1997-1432
- Languages: English
- Source: Proceedings of the 1996 International Compressor Engineering Conference at Purdue.
- Publication date: 1996/07/23
- Document available for consultation in the library of the IIR headquarters only.
Links
See other articles from the proceedings (49)
See the conference proceedings
Indexing
-
Themes:
HCFCs;
Compressors;
Blends - Keywords: R410A; R407C; Comparison; R22; Performance; Rotary compressor; Scroll compressor; Compressor
-
Simulation of the scroll-type compressor using ...
- Author(s) : CHANG Y. C., LAI C. F., SHYU R. J., et al.
- Date : 1999/09/19
- Languages : English
- Source: 20th International Congress of Refrigeration: Refrigeration into the Third Millennium.
- Formats : PDF
View record
-
A comparison of different generalised modelling...
- Author(s) : LEE C. K., LAM H. N.
- Date : 2013/06
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 36 - n. 4
- Formats : PDF
View record
-
Computational comparison of R22 and R407C air c...
- Author(s) : VAISMAN I. B.
- Date : 1998/07/14
- Languages : English
- Source: Proceedings of the 1998 Purdue International Refrigeration Conference.
View record
-
Systemvergleich für R22-Ersatzstoffe: R407C und...
- Author(s) : KÖNIG H.
- Date : 1998/10
- Languages : German
- Source: KI Luft Kältetech. - vol. 34 - n. 10
View record
-
Vergleich der Kältemittel R22, R410A und R407C ...
- Author(s) : HELLMANN J., DÖRING R.
- Date : 1996/11/20
- Languages : German
- Source: DKV-Tagungsbericht 23. 1996 Leipzig.
View record