Condensate subcooling near tube exit during horizontal in-tube condensation.

Author(s) : HASHIZUME K., ABE N., OZEKI T.

Type of article: Article

Summary

In the experiment, test fluids used were refrigerants R113, R11, R114, and R12. Condensate subcoolings of larger than 10 K were measured, even before condensation was completed, and data of condensate temperature profiles were obtained along the adiabatic section following the condensing section. Analysis, based on a nonequilibrium heat transfer model, could closely predict experimental data both for condensate subcooling at the condensing section exit and for condensate temperature profiles in the adiabatic section.

Details

  • Original title: Condensate subcooling near tube exit during horizontal in-tube condensation.
  • Record ID : 1993-0163
  • Languages: English
  • Source: Heat Transf. Eng. - vol. 13 - n. 1
  • Publication date: 1992/01