Critical heat flux in multi-microchannel copper elements with low pressure refrigerants.

Author(s) : PARK J. E., THOME J. R.

Type of article: Article

Summary

New saturated critical heat flux (CHF) data have been obtained experimentally in two different multi-microchannel heat sinks made in copper with three low pressure refrigerants (R134a, R236fa, R245fa). One of the test sections has 20 parallel rectangular channels, 467 micrometers wide and 4052 micrometers deep while the second has 29 channels, 199 micrometers wide and 756 micrometers deep. The microchannels are 30 mm long in the flow direction where a 20 mm length in the middle is heated with an electrical resistance deposited on a silicon plate. Base CHF values were measured from 37 to 342 W/cm2 for mass velocities from 100 to 4000 kg/m2.s. When increasing the mass velocity, CHF was observed to increase while the rate of increase was slower at high velocities. While CHF increased moderately with large inlet subcooling (e.g. 20 K) in the H = 4052 micrometer channels, inlet subcooling seemed to play less a role as the channel size decreased. CHF showed reversed tendency with increasing inlet saturation temperature depending on the flow condition and the channel size. The experimental data were compared with existing prediction methods. The data demonstrated good agreement with several predictive methods using the heated equivalent diameter and the actual mass velocity to implement the circular tube correlations. [Reprinted with permission from Elsevier. Copyright, 2009].

Details

  • Original title: Critical heat flux in multi-microchannel copper elements with low pressure refrigerants.
  • Record ID : 2010-1405
  • Languages: English
  • Source: International Journal of Heat and Mass Transfer - vol. 53 - n. 1-3
  • Publication date: 2010/01/15
  • DOI: http://dx.doi.org/10.1016/j.ijheatmasstransfer.2009.09.047

Links


See other articles in this issue (2)
See the source