IIR document

DESCRIPTION OF THE 11 MW HEAT PUMP PLANT IN OESTERSUND, SWEDEN.

Author(s) : MOSER F.

Summary

IN 1983 IT WAS DECIDED TO INSTALL A HEAT PUMP WITH A TWO-STAGE CENTRIFUGAL COMPRESSOR HAVING A NOMINAL CAPACITY OF 11 MW. OPERATING SINCE OCTOBER 1984, IT PRODUCED 23,000 MWH HEAT IN 2,630 HRS, WITH AN AVERAGE COP OF 2.9. AS THE HEAT SOURCE, FILTERED SEWAGE WATER WAS USED, COOLED IN A SHELL AND TUBE EVAPORATOR. THE BAD QUALITY OF SEWAGE WATER RESULTED IN A VERY RAPID FOULING OF THE EVAPORATOR, THUS REQUIRING THE INSTALLATION OF AN AUTOMATIC CLEANING SYSTEM.

Available documents

Format PDF

Pages: 1985-3

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: DESCRIPTION OF THE 11 MW HEAT PUMP PLANT IN OESTERSUND, SWEDEN.
  • Record ID : 1987-1166
  • Languages: English
  • Source: Systems and components for large heat pumps.
  • Publication date: 1985/06/19

Links


See other articles from the proceedings (34)
See the conference proceedings