Experimental analysis and simulation of coils in an air-to-water heat pump operating at full and part load conditions.
Number: 2325
Author(s) : KRISHNAMURTI S., ORTEGA I., SIERES J., AUTE V.
Summary
Dual mode heat pumps are a crucial technology to minimize emissions from cooling and heating systems as we strive to achieve a decarbonized future. With the use of variable speed drives, these heat pumps have become more efficient. However, under extreme part load conditions, the control of these devices is challenging and current heat exchanger model capabilities cannot fully handle such phenomenon. This research presents comprehensive experimental analysis of an air-coil used in an R410A air-to-water heat pump. The coil has 2 rows of 36 tubes each. The refrigerant flow is distributed in 5 refrigerant circuits of 7 hairpins each (14 tubes per circuit), arranged one on top of the other, plus an additional hairpin located at the bottom of the coil that collects the refrigerant flow from the 5 circuits. In order to estimate the refrigerant temperature profiles in the coil circuitry, temperature sensors were attached on different locations of the tubes of the coil. Airflow maldistribution measurements were also conducted. Experiments were performed combining different compressor and fan speed values. The experimental temperature profiles suggest that the refrigerant distribution in each circuit is not equal and that some refrigerant accumulation and/or low refrigerant flow occurs in the lower refrigerant circuits. This is in part due to gravity, and the effect is more pronounced when operating the unit with low compressor speeds. The experimental data were used to validate existing air-to-refrigerant
heat exchanger models and to identify future model development and validation initiatives. The predicted performance agreed with measured data within ±5%, but this deviation was significantly higher for low mass flux conditions, highlighting the need for improved modeling of gravity for accurate predictions of refrigerant mass flow
maldistribution in headers.
Available documents
Format PDF
Pages: 10 p.
Available
Free
Details
- Original title: Experimental analysis and simulation of coils in an air-to-water heat pump operating at full and part load conditions.
- Record ID : 30033176
- Languages: English
- Subject: Technology
- Source: 2024 Purdue Conferences. 20th International Refrigeration and Air-Conditioning Conference at Purdue.
- Publication date: 2024/07/17
Links
See other articles from the proceedings (187)
See the conference proceedings
-
Experimental analytical investigation on surfac...
- Author(s) : HU D., GUO B., XU C., et al.
- Date : 2007/08/21
- Languages : English
- Source: ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
- Formats : PDF
View record
-
Experimental study of interaction between frost...
- Author(s) : GUO X., YANG B., WANG W., et al.
- Date : 2007/08/21
- Languages : English
- Source: ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
- Formats : PDF
View record
-
The study on the evaporator of an air-cooled he...
- Author(s) : ZHANG Z., TIAN J. J.
- Date : 2007/08/21
- Languages : English
- Source: ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
- Formats : PDF
View record
-
An improved moving boundary heat exchanger mode...
- Author(s) : QIAO H., AUTE V., RADERMACHER R.
- Date : 2014/07/14
- Languages : English
- Source: 2014 Purdue Conferences. 15th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
View record
-
Fan-less heat exchanger concept for CO2 heat pu...
- Author(s) : NEKSÅ P., HOGGEN R. L., AFLEKT K., et al.
- Date : 2004/08/01
- Languages : English
- Source: Natural Working Fluids 2004: 6th IIR-Gustav Lorentzen Conference
- Formats : PDF
View record