Mathematical and experimental study on solar ejector cooling system using new refrigerant of r236fa.

Number: pap. ID: 903

Author(s) : ZHANG B., ZUO J. X., LV J. S., et al.

Summary

Based on the analysis of solar ejector cooling system and comparison among different refrigerants, a solar ejector cooling system using a new refrigerant, R236fa, was developed. First, the operating performance of the solar ejector cooling system was simulated. Then the experimental study on the system using refrigerants R236fa, R141b and R123 was carried out with evaporator temperature from 5 to 10°C, condenser temperature from 30 to 36°C and generator temperature from 82 to 94°C. The results show that with refrigerant R236fa the optimum COP of the ejector cooling system was 0.413 and the optimum overall COP of the solar ejector cooling system was 0.243.

Available documents

Format PDF

Pages: 8 p.

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Mathematical and experimental study on solar ejector cooling system using new refrigerant of r236fa.
  • Record ID : 30001637
  • Languages: English
  • Source: Proceedings of the 23rd IIR International Congress of Refrigeration: Prague, Czech Republic, August 21-26, 2011. Overarching theme: Refrigeration for Sustainable Development.
  • Publication date: 2011/08/21