Nucleate boiling performance of R22, R123, R134a, R410A, and R407C on smooth and enhanced tubes.

Summary

Experiments were conducted at saturation temperatures of 0 and 20 deg C. For the W-TX tube at a given saturation temperature, the heat transfer coefficients for R410A are the largest and for R123 are the lowest. For the highly structured surface, W-B tube, the heat transfer coefficients for R22 and R410A are comparable, while the heat transfer coefficients for R407C are the lowest.

Details

  • Original title: Nucleate boiling performance of R22, R123, R134a, R410A, and R407C on smooth and enhanced tubes.
  • Record ID : 1999-2847
  • Languages: English
  • Source: ASHRAE Transactions. 1998 Winter Meeting, San Francisco, CA.
  • Publication date: 1998
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles from the proceedings (79)
See the conference proceedings