Optimal distribution of condenser area for retrofits.

Author(s) : JOHANSSON A., LUNDQVIST P.

Summary

Test results from field retrofit situations, where R22 has been changed to Isceon 59 and R407C in two identical chillers, shows that both substitutes require more subcooling than R22 to give the system a satisfying performance. To achieve the same efficiency, COP2, with Isceon 59 as with R22, one had to add approximately 25 per cent more refrigerant. A computer model of a system consisting of coaxial heat exchangers, with refrigerant in the inner tubes, has been made. In the model five R22 substitutes (R134a, propane, R404A, R407C and Isceon 59) and R22 were compared. Areas for subcooling are studied, as are refrigerant amounts.