Optimal distribution of condenser area for retrofits.
Author(s) : JOHANSSON A., LUNDQVIST P.
Summary
Test results from field retrofit situations, where R22 has been changed to Isceon 59 and R407C in two identical chillers, shows that both substitutes require more subcooling than R22 to give the system a satisfying performance. To achieve the same efficiency, COP2, with Isceon 59 as with R22, one had to add approximately 25 per cent more refrigerant. A computer model of a system consisting of coaxial heat exchangers, with refrigerant in the inner tubes, has been made. In the model five R22 substitutes (R134a, propane, R404A, R407C and Isceon 59) and R22 were compared. Areas for subcooling are studied, as are refrigerant amounts.
Details
- Original title: Optimal distribution of condenser area for retrofits.
- Record ID : 1999-3362
- Languages: English
- Source: Proceedings of the 1998 Purdue International Refrigeration Conference.
- Publication date: 1998/07/14
- Document available for consultation in the library of the IIR headquarters only.
Links
See other articles from the proceedings (67)
See the conference proceedings
Indexing
-
Themes:
HCFCs;
HFCs;
Hydrocarbons;
Blends - Keywords: Refrigerating circuit; R407C; R134a; R404A; R22; Subcooling; Propane; Performance; Retrofitting; Refrigerant charge
-
Anforderungen an Komponenten- und Systemauslegu...
- Author(s) : RENZ H.
- Date : 1999/02
- Languages : German
- Source: Kälte + Klimatechnik (Die) - vol. 52 - n. 2
View record
-
Koudemiddelen voor de toekomst: een praktische ...
- Author(s) : MORLEY J. R.
- Date : 1999/12
- Languages : Dutch
- Source: Koude & Luchtbehandeling - vol. 92 - n. 12
View record
-
Experimental evaluation of five refrigerants as...
- Author(s) : MEYER J. P.
- Date : 2000/06/24
- Languages : English
- Source: ASHRAE Transactions. 2000 ASHRAE Annual Meeting, Minneapolis, Minnesota + CD-ROM.
View record
-
Effect of refrigerant choice.
- Author(s) : HUNDY G. F., PHAM H. M.
- Date : 2001/11/01
- Languages : English
- Source: Efficient air conditioning: the role of refrigeration. Conference proceedings.
View record
-
R22 Retrofit: one problem, many solutions.
- Author(s) : LUNDQVIST P. G.
- Date : 1999/09/19
- Languages : English
- Source: 20th International Congress of Refrigeration: Refrigeration into the Third Millennium.
- Formats : PDF
View record