Performance of R-432A to replace HCFC-22 in residential air conditioners and heat pumps.
Author(s) : PARK K. J., LEE C. H., JUNG D.
Summary
In this study, thermodynamic performance of R-432A and HCFC-22 is measured in a heat pump bench tester under both air conditioning and heat pumping conditions. R-432A has no ozone depletion potential and very low greenhouse warming potential of less than 5. R-432A also offers a similar vapour pressure to that of HCFC-22 for 'drop-in' replacement. Test results showed that the coefficient of performance and capacity of R-432A are 8.5-8.7 and 1.9-6.4% higher than those of HCFC-22 for both conditions. The compressor discharge temperature of R-432A is 14.1-17.3°C lower than that of HCFC-22 while the amount of charge for R-432A is 50% lower than that of HCFC-22 due to its low density. Overall, R-432A is a good long term 'drop-in' environmentally friendly alternative to replace HCFC-22 in residential air conditioners and heat pumps due to its excellent thermodynamic and environmental properties.
Available documents
Format PDF
Available
Public price
20 €
Member price*
15 €
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: Performance of R-432A to replace HCFC-22 in residential air conditioners and heat pumps.
- Record ID : 2009-1783
- Languages: English
- Source: 2008 Purdue Conferences. 19th International Compressor Engineering Conference at Purdue & 12th International Refrigeration and Air-Conditioning Conference at Purdue [CD-ROM].
- Publication date: 2008/07/14
Links
- See translations: Prestaciones del R432A al sustituir el HCFC-22 en acondicionadores de aire residenciales y en bombas de calor.
See other articles from the proceedings (125)
See the conference proceedings
Indexing
-
Themes:
HCFCs;
Residential heat-pumps - Keywords: Comparison; Measurement; Air conditioner; R432a; R22; Heat pump; Performance; Residential building; COP; Refrigerant; Air conditioning
-
Prestaciones del R432A al sustituir el HCFC-22 ...
- Author(s) : PARK K. J., LEE C. H., JUNG D.
- Date : 2009/10
- Languages : Spanish
- Source: Frío Calor Aire acondicionado - vol. 37 - n. 418
- Formats : PDF
View record
-
Experimental performance of R432A to replace R2...
- Author(s) : PARK K. J., SHIM Y. B., JUNG D.
- Date : 2009/02
- Languages : English
- Source: Applied Thermal Engineering - vol. 29 - n. 2-3
View record
-
Comparison of R407C and R410A with R22 in a 10....
- Author(s) : LINTON J. W., SNELSON W. K., HEARTY P. F., TRIEBE A. R., MURPHY F. T., LOW R. E., GILBERT B. E.
- Date : 1996/07/23
- Languages : English
- Source: Proceedings of the 1996 Purdue International Refrigeration Conference.
View record
-
Evaluation on the application of R-410A in resi...
- Author(s) : CHEN W., SPATZ M. W., YANA MOTTA S., et al.
- Date : 2007/08/21
- Languages : English
- Source: ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
- Formats : PDF
View record
-
Comparison of practical performance between CO<...
- Author(s) : AARLIEN R., FRIVIK P. E.
- Date : 1998/06/02
- Languages : English
- Source: Natural Refrigerants, Energy Efficiency, Cost and Safety. Natural Working Fluids '98. IIR-Gustav Lorentzen Conference.
- Formats : PDF
View record