IIR document
Potential enhancement investigation of commercial R744 refrigeration systems based on avoidable and unavoidable exergy destruction concepts.
Number: pap. 1041
Author(s) : GULLO P., CORTELLA G., MINETTO S.
Summary
In this paper, the actual feasible reduction in the inefficiencies occurring in two different commercial CO2 refrigeration systems was evaluated. The analysis was based on the calculation of the avoidable and unavoidable irreversibilities taking place in their components. The systems under investigation, which were a R744 refrigeration system with parallel compression and a R744 refrigerating plant with dedicated mechanical subcooling, were assessed by taking into account the design outdoor temperature of 30 °C. A cooling capacity of 100 kW and an evaporating temperature of -10 °C were selected, while the global efficiencies of all the
chosen compressors were obtained by using some manufacturers’ selection software. The results revealed that, in both the selected cases, over 60% of the irreversibilities could be brought down. In particular, the inefficiencies of all the compressors were almost totally avoidable, whereas only half of the exergy destruction related to both the gas coolers and the evaporators could be actually reduced. The auxiliary compressor and the subcooling loop were accountable for14.6% and 25% of the total avoidable inefficiencies associated with their corresponding cycles.
Available documents
Format PDF
Pages: 8 p.
Available
Public price
20 €
Member price*
Free
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: Potential enhancement investigation of commercial R744 refrigeration systems based on avoidable and unavoidable exergy destruction concepts.
- Record ID : 30019111
- Languages: English
- Source: 12th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2016). Proceedings. Édimbourg, United Kingdom, August 21st-24th 2016.
- Publication date: 2016/08/21
- DOI: http://dx.doi.org/10.18462/iir.gl.2016.1041
Links
See other articles from the proceedings (140)
See the conference proceedings
Indexing
-
Themes:
CO2;
Supermarkets, display cabinets - Keywords: Refrigerating system; Exergy; R744; Supermarket; Subcooling; Performance; Compressor
-
COP improvement of a CO2 refrigeration system w...
- Author(s) : WENZEL M., HESSE U.
- Date : 2012/07/16
- Languages : English
- Source: 2012 Purdue Conferences. 14th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
View record
-
Experimental COP enhancement of a CO2 transcrit...
- Author(s) : ARANGUREN P., SÁNCHEZ D., CASI A., ARAIZ M., ASTRAIN D., CABELLO R.
- Date : 2020/11/11
- Languages : Spanish
- Source: X Congreso Ibérico y VIII Congreso Iberoamericano de Ciencias y Técnicas del Frío, CYTEF 2020.
- Formats : PDF
View record
-
Efficiency enhancement by subcooling the carbon...
- Author(s) : HANSLIK F., SUESS J., KOEHLER J.
- Date : 2018/07/09
- Languages : English
- Source: 2018 Purdue Conferences. 17th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
View record
-
Supermarket application. Effects of sub-cooling...
- Author(s) : MAZZOLA D., SHEEHAN J., BORTOLUZZI D., et al.
- Date : 2016/08/21
- Languages : English
- Source: 12th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2016). Proceedings. Édimbourg, United Kingdom, August 21st-24th 2016.
- Formats : PDF
View record
-
Energy evaluation of the mechanical subcooling ...
- Author(s) : NEBOT-ANDRÉS L., LLOPIS R., CATALÁN-GIL J., et al.
- Date : 2018/06/18
- Languages : English
- Source: 13th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2018). Proceedings. Valencia, Spain, June 18-20th 2018.
- Formats : PDF
View record