IIR document

Thermodynamic analysis of optimum condensing temperature of cascade-condenser for CO2/NH3 cascade refrigeration systems.

Summary

This study analyses a cascade refrigeration system utilizing carbon dioxide and ammonia as refrigerants, to find the optimum condensing temperature of the cascade-condenser in which the system attained the maximum COP and the minimum exergy destruction. The results indicate that the optimum condensing temperature of the cascade condenser is -18°C under the condensing temperature of 35°C and the evaporating temperature of -50°C. The analytical results of this study are useful for the design and development of CO2/NH3 cascade refrigeration systems and related equipment.

Available documents

Format PDF

Pages: 2005-2

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Thermodynamic analysis of optimum condensing temperature of cascade-condenser for CO2/NH3 cascade refrigeration systems.
  • Record ID : 2006-1176
  • Languages: English
  • Source: Ammonia Refrigerating Systems, Renewal and Improvement.
  • Publication date: 2005/05/06