Thermodynamic design data for absorption heat pump systems operating on monomethylamine-water. 1. Cooling. 2. Heating. 3. Simultaneous cooling and heating.

Author(s) : PILATOWSKY I., RIVERA W., BEST R., HOLLAND F. A.

Type of article: Article

Summary

The Gibbs phase rule and thermodynamic properties of the working pair limit the choice of operating temperatures. For any combination of temperatures, the concentrations in the absorber and the generator and hence the flow ratios are fixed. For any particular working pair, the COP is related to the flow ratio. Tables of possible combinations of operating temperatures and concentrations have been presented for monomethylamine-water absorption systems for cooling. The interactions of operating temperatures have been illustrated graphically.

Details

  • Original title: Thermodynamic design data for absorption heat pump systems operating on monomethylamine-water. 1. Cooling. 2. Heating. 3. Simultaneous cooling and heating.
  • Record ID : 1996-1828
  • Languages: English
  • Source: Heat Recov. Syst. CHP - vol. 15 - n. 6
  • Publication date: 1995/08

Links


See other articles in this issue (4)
See the source